XP Medium voltage, single core cable, nonshielded XLPE/PE

Products

XP 5KV 8AWG 19H NEGRO DGAC

Nexans ref. 10033623

  • Packaging: Cut to length (2000m)

 

XP 5kV 8AWG 19H MORADO DGAC.

Nexans ref. 10048952

  • Packaging: Cut to length (2000m)

 

Description

Description

Standards

  • National
    ASTM B 3; ASTM B 496; ASTM B 8; ICEA S-96-659

Applications

Power nonshielded cable for fixed installations, used for connection of transformers, switchgears, GIS substations, motors, generators, feeders in distribution networks. Suitable to be installed directly buried, buried in ducts, in conduits or in free air.

Construction: Singlecore cable.

Conductor: stranded copper conductor. For AWG and kcmil sizes according to ASTM B-3, ASTM B8 and ASTM B-496 according to requirements of ICEA S-96-659. 

Conductor shield: Extruded semiconducting material.

Insulation: crosslinked polyethilene (XLPE)  with excellent electrical properties, good resistance to ozone and chemical agents.

Oversheath: Polyethylene (PE),  resistant to weather and UV radiation. Color upon request.

 

Marking: NEXANS CHILE XP "size" "Rated voltage" Cu XLPE 90°C  "Manuf. order"  "Date"

 

 

 

 

INSTALLATION CONDITIONS FOR CURRENT CARRYING CAPACITIES_MV CABLES

(1) Current carrying capacities based on ICEA P-46-426, for installations were ducts and cables are not directly exposed to solar radiation.

De-rating factors must be applied according to specific installation conditions.

INSTALLATION CONDITIONS FOR CURRENT CARRYING CAPACITIES_MV CABLES

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Outer sheath
PE

Dimensional characteristics

Dimensional characteristics

Conductor cross-section (AWG/KCMIL)
8
Conductor cross-section
8.37 mm²

Electrical characteristics

Electrical characteristics

Operating voltage
5 kV
Insulation Level
100 %
Perm current rating in air 40°C
82 A
Permissible current rating buried 20°C
97 A
Perm. Current in duct 20°C
79 A

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Overload maximum core temperature
130 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-10 °C
Oil resistance
ICEA S-93-639 (70°C/4h)
U.V resistance
UL 1581

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close