H07Z1-K 4mm2 Azul R100m

Description

Description

Standards

  • Product
    EN 50525-3-31; IEC 60228
  • Test
    IEC 60332-1-2; IEC 60332-3-24; IEC 60754-1; IEC 60754-2; IEC 61034-2

Uses / Applications
General use for interior power and lighting circuits in dry environments. For installations in places of concentration of people such as: hospitals, casinos, supermarkets, offices, shopping centers, classrooms, auditoriums, etc. These conductors increase the safety of people and property in the event of a fire.

Construction
FormationCopper monoconductor.
Conductor: Soft copper cable, class 5 flexible stranded according to IEC 60228.
InsulationFREETOX® compound, Low fire hazard thermoplastic, Halogen free with low smoke emission, low toxicity, highly flame retardant and non-fire propagation. Available in blue, black, red, white or green colors.

MarkingNexans FREETOX-FLEX H07Z1-K (AS) TIPO 2  "Size" 0,45/0,75 kV 70°C INGCER E-021-14-11415 "Date" CHILE

INSTALATION CONDITIONS FOR CURRENT CARRYING CAPACITY (70°C SINGLE CORE)

Current carrying capacities based on table N°4.4 of RIC N°4, for installation and cables not directly exposed to solar radiation.

Perm rating in duct 30°C (Current in duct at 30°C): Up to three single conductors with load installed in ducts or channels attached to walls, ambient temperature 30°C.. Installation Method B1 according to RIC N°4

Permissible current rating in duct (Current in embedded duct at 30°C): Up to three single conductors with load installed in ducts embedded in walls, ambient temperature 30°C. Method A1 according to RIC N°4

Current capacity correction factors must be considered according to the specific installation conditions.

INSTALATION CONDITIONS 70C SINGLE CORE

NOTES / VOLTAGE DROP

The indicated values ​​consider single-phase circuits in alternating current at 50Hz. To calculate the voltage drop in Volts, you must multiply the value indicated in the table [V/A.km] by the current to be transported in [A] by the length of the circuit in [km]

Certificate SEC H07Z1-K

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Conductor flexibility
Class 5
Number of conductors
1
Insulation
LFH (Low Fire hazard) compound
Insulation colour
Blue
Halogen free
IEC 60754-1
Lead free
Yes

Dimensional characteristics

Dimensional characteristics

Phase Conductor Cross Section
4 mm²
Conductor cross-section
4 mm²
Total number of wires
49
Nominal diameter of wires
0.3 mm
Average insulation thickness
0.8 mm
Outer Diameter
4.5 mm
Approximate weight
47 kg/km
Nominal outer diameter
4.5 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
450/750 V
Max. DC resistance of the conductor at 20°C
4.95 Ohm/km
Conductor AC resistance at 50 Hz
5.98 Ohm/km
Perm current rating in duct 30°C
28 A
Permissible current rating in duct 
24 A
Voltage Drop
12.0 V/A.km

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Class 5 IEC 60228

Usage characteristics

Usage characteristics

Laying operation bending radius
18 mm
Max. conductor temperature in service
70 °C
Short-circuit max. conductor temperature
160 °C
Flame retardant
IEC 60332-1-2
Fire retardant
IEC 60332-3-24 (cat C)
Smoke density
IEC 61034-2
Packaging
Coil
Length
100 m

Resources

Resources

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close