MULTI-FLEX® (RV-K)

Products

1x14AWG

Nexans ref. 10003102

  • Conductor cross-section: 2.08 mm²
  • Conductor cross-section (AWG/KCMIL): 14
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 31 A
  • Permissible current rating buried/duct 20°C: 30 A
  • Perm current rating in duct 30°C: 24 A
  • Perm current rating in air 30°C: - A

 

1x12AWG

Nexans ref. 10003129

  • Conductor cross-section: 3.31 mm²
  • Conductor cross-section (AWG/KCMIL): 12
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 39 A
  • Permissible current rating buried/duct 20°C: 38 A
  • Perm current rating in duct 30°C: 31 A
  • Perm current rating in air 30°C: - A

 

1x8AWG

Nexans ref. 10003138

  • Conductor cross-section: 8.37 mm²
  • Conductor cross-section (AWG/KCMIL): 8
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 89 A
  • Permissible current rating buried/duct 20°C: 63 A
  • Perm current rating in duct 30°C: 59 A
  • Perm current rating in air 30°C: 68 A

 

1x10AWG

Nexans ref. 10003134

  • Conductor cross-section: 5.26 mm²
  • Conductor cross-section (AWG/KCMIL): 10
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 69 A
  • Permissible current rating buried/duct 20°C: 48 A
  • Perm current rating in duct 30°C: 39 A
  • Perm current rating in air 30°C: 50 A

 

1x6AWG

Nexans ref. 10003144

  • Conductor cross-section: 13.3 mm²
  • Conductor cross-section (AWG/KCMIL): 6
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 114 A
  • Permissible current rating buried/duct 20°C: 80 A
  • Perm current rating in duct 30°C: 79 A
  • Perm current rating in air 30°C: 93 A

 

1x4AWG

Nexans ref. 10003153

  • Conductor cross-section: 21.2 mm²
  • Conductor cross-section (AWG/KCMIL): 4
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 147 A
  • Permissible current rating buried/duct 20°C: 103 A
  • Perm current rating in duct 30°C: 105 A
  • Perm current rating in air 30°C: 126 A

 

1x2AWG

Nexans ref. 10003157

  • Conductor cross-section: 33.6 mm²
  • Conductor cross-section (AWG/KCMIL): 2
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 189 A
  • Permissible current rating buried/duct 20°C: 132 A
  • Perm current rating in duct 30°C: 141 A
  • Perm current rating in air 30°C: 172 A

 

1x1AWG

Nexans ref. 10003161

  • Conductor cross-section: 42.4 mm²
  • Conductor cross-section (AWG/KCMIL): 1
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 216 A
  • Permissible current rating buried/duct 20°C: 150 A
  • Perm current rating in duct 30°C: 163 A
  • Perm current rating in air 30°C: 200 A

 

1x1/0AWG

Nexans ref. 10003163

  • Conductor cross-section: 53.5 mm²
  • Conductor cross-section (AWG/KCMIL): 1/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 245 A
  • Permissible current rating buried/duct 20°C: 170 A
  • Perm current rating in duct 30°C: 188 A
  • Perm current rating in air 30°C: 234 A

 

1x2/0AWG

Nexans ref. 10003166

  • Conductor cross-section: 67.4 mm²
  • Conductor cross-section (AWG/KCMIL): 2/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 278 A
  • Permissible current rating buried/duct 20°C: 192 A
  • Perm current rating in duct 30°C: 217 A
  • Perm current rating in air 30°C: 273 A

 

1x3/0AWG

Nexans ref. 10003167

  • Conductor cross-section: 85 mm²
  • Conductor cross-section (AWG/KCMIL): 3/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 315 A
  • Permissible current rating buried/duct 20°C: 218 A
  • Perm current rating in duct 30°C: 251 A
  • Perm current rating in air 30°C: 318 A

 

1x4/0AWG

Nexans ref. 10003170

  • Conductor cross-section: 107 mm²
  • Conductor cross-section (AWG/KCMIL): 4/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 362 A
  • Permissible current rating buried/duct 20°C: 248 A
  • Perm current rating in duct 30°C: 290 A
  • Perm current rating in air 30°C: 371 A

 

3X14AWG

Nexans ref. 10003109

  • Conductor cross-section: 2.08 mm²
  • Conductor cross-section (AWG/KCMIL): 14
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 31 A
  • Permissible current rating buried/duct 20°C: 30 A
  • Perm current rating in duct 30°C: 24 A
  • Perm current rating in air 30°C: 28 A

 

3X12AWG

Nexans ref. 10003128

  • Conductor cross-section: 3.31 mm²
  • Conductor cross-section (AWG/KCMIL): 12
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 39 A
  • Permissible current rating buried/duct 20°C: 38 A
  • Perm current rating in duct 30°C: 31 A
  • Perm current rating in air 30°C: 38 A

 

3X10AWG

Nexans ref. 10003133

  • Conductor cross-section: 5.26 mm²
  • Conductor cross-section (AWG/KCMIL): 10
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 69 A
  • Permissible current rating buried/duct 20°C: 48 A
  • Perm current rating in duct 30°C: 38 A
  • Perm current rating in air 30°C: 50 A

 

3X8AWG

Nexans ref. 10021291

  • Conductor cross-section: 8.37 mm²
  • Conductor cross-section (AWG/KCMIL): 8
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 89 A
  • Permissible current rating buried/duct 20°C: 63 A
  • Perm current rating in duct 30°C: 54 A
  • Perm current rating in air 30°C: 67 A

 

3X6AWG

Nexans ref.

  • Conductor cross-section: 13.3 mm²
  • Conductor cross-section (AWG/KCMIL): 6
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 114 A
  • Permissible current rating buried/duct 20°C: 80 A
  • Perm current rating in duct 30°C: 72 A
  • Perm current rating in air 30°C: 89 A

 

3X4AWG

Nexans ref.

  • Conductor cross-section: 21.2 mm²
  • Conductor cross-section (AWG/KCMIL): 4
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 147 A
  • Permissible current rating buried/duct 20°C: 103 A
  • Perm current rating in duct 30°C: 95 A
  • Perm current rating in air 30°C: 114 A

 

3X2AWG

Nexans ref.

  • Conductor cross-section: 33.6 mm²
  • Conductor cross-section (AWG/KCMIL): 2
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 189 A
  • Permissible current rating buried/duct 20°C: 132 A
  • Perm current rating in duct 30°C: 125 A
  • Perm current rating in air 30°C: 154 A

 

3X1AWG

Nexans ref.

  • Conductor cross-section: 42.4 mm²
  • Conductor cross-section (AWG/KCMIL): 1
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 216 A
  • Permissible current rating buried/duct 20°C: 150 A
  • Perm current rating in duct 30°C: 144 A
  • Perm current rating in air 30°C: 178 A

 

3X1/0AWG

Nexans ref.

  • Conductor cross-section: 53.5 mm²
  • Conductor cross-section (AWG/KCMIL): 1/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 245 A
  • Permissible current rating buried/duct 20°C: 170 A
  • Perm current rating in duct 30°C: 165 A
  • Perm current rating in air 30°C: 207 A

 

3X2/0AWG

Nexans ref.

  • Conductor cross-section: 67.4 mm²
  • Conductor cross-section (AWG/KCMIL): 2/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 278 A
  • Permissible current rating buried/duct 20°C: 192 A
  • Perm current rating in duct 30°C: 190 A
  • Perm current rating in air 30°C: 240 A

 

3X3/0AWG

Nexans ref.

  • Conductor cross-section: 85 mm²
  • Conductor cross-section (AWG/KCMIL): 3/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 315 A
  • Permissible current rating buried/duct 20°C: 218 A
  • Perm current rating in duct 30°C: 218 A
  • Perm current rating in air 30°C: 278 A

 

3X4/0AWG

Nexans ref.

  • Conductor cross-section: 107 mm²
  • Conductor cross-section (AWG/KCMIL): 4/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 362 A
  • Permissible current rating buried/duct 20°C: 248 A
  • Perm current rating in duct 30°C: 251 A
  • Perm current rating in air 30°C: 322 A

 

4X10AWG

Nexans ref. 10017183

  • Conductor cross-section: 5.26 mm²
  • Conductor cross-section (AWG/KCMIL): 10
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 69 A
  • Permissible current rating buried/duct 20°C: 48 A
  • Perm current rating in duct 30°C: 38 A
  • Perm current rating in air 30°C: 50 A

 

4X14AWG

Nexans ref. 10021255

  • Conductor cross-section: 2.08 mm²
  • Conductor cross-section (AWG/KCMIL): 14
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 31 A
  • Permissible current rating buried/duct 20°C: 30 A
  • Perm current rating in duct 30°C: 24 A
  • Perm current rating in air 30°C: 28 A

 

4X12AWG

Nexans ref. 10003125

  • Conductor cross-section: 3.31 mm²
  • Conductor cross-section (AWG/KCMIL): 12
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 39 A
  • Permissible current rating buried/duct 20°C: 38 A
  • Perm current rating in duct 30°C: 31 A
  • Perm current rating in air 30°C: 38 A

 

4X8AWG

Nexans ref. 10014494

  • Conductor cross-section: 8.37 mm²
  • Conductor cross-section (AWG/KCMIL): 8
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 89 A
  • Permissible current rating buried/duct 20°C: 63 A
  • Perm current rating in duct 30°C: 54 A
  • Perm current rating in air 30°C: 67 A

 

4X1AWG

Nexans ref.

  • Conductor cross-section: 42.4 mm²
  • Conductor cross-section (AWG/KCMIL): 1
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 216 A
  • Permissible current rating buried/duct 20°C: 150 A
  • Perm current rating in duct 30°C: 144 A
  • Perm current rating in air 30°C: 178 A

 

4X6AWG

Nexans ref. 10014495

  • Conductor cross-section: 13.3 mm²
  • Conductor cross-section (AWG/KCMIL): 6
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 114 A
  • Permissible current rating buried/duct 20°C: 80 A
  • Perm current rating in duct 30°C: 72 A
  • Perm current rating in air 30°C: 89 A

 

4X4AWG

Nexans ref. 10003152

  • Conductor cross-section: 21.2 mm²
  • Conductor cross-section (AWG/KCMIL): 4
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 147 A
  • Permissible current rating buried/duct 20°C: 103 A
  • Perm current rating in duct 30°C: 95 A
  • Perm current rating in air 30°C: 114 A

 

4X2AWG

Nexans ref. 10014496

  • Conductor cross-section: 33.6 mm²
  • Conductor cross-section (AWG/KCMIL): 2
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 189 A
  • Permissible current rating buried/duct 20°C: 132 A
  • Perm current rating in duct 30°C: 125 A
  • Perm current rating in air 30°C: 154 A

 

4X1/0AWG

Nexans ref.

  • Conductor cross-section: 53.5 mm²
  • Conductor cross-section (AWG/KCMIL): 1/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 245 A
  • Permissible current rating buried/duct 20°C: 170 A
  • Perm current rating in duct 30°C: 165 A
  • Perm current rating in air 30°C: 207 A

 

4X2/0AWG

Nexans ref.

  • Conductor cross-section: 67.4 mm²
  • Conductor cross-section (AWG/KCMIL): 2/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 278 A
  • Permissible current rating buried/duct 20°C: 192 A
  • Perm current rating in duct 30°C: 190 A
  • Perm current rating in air 30°C: 240 A

 

4X3/0AWG

Nexans ref.

  • Conductor cross-section: 85 mm²
  • Conductor cross-section (AWG/KCMIL): 3/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 315 A
  • Permissible current rating buried/duct 20°C: 218 A
  • Perm current rating in duct 30°C: 218 A
  • Perm current rating in air 30°C: 278 A

 

4X4/0AWG

Nexans ref.

  • Conductor cross-section: 107 mm²
  • Conductor cross-section (AWG/KCMIL): 4/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 362 A
  • Permissible current rating buried/duct 20°C: 248 A
  • Perm current rating in duct 30°C: 251 A
  • Perm current rating in air 30°C: 322 A

 

5X14AWG

Nexans ref. 10022092

  • Conductor cross-section: 2.08 mm²
  • Conductor cross-section (AWG/KCMIL): 14
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 31 A
  • Permissible current rating buried/duct 20°C: 30 A
  • Perm current rating in duct 30°C: 24 A
  • Perm current rating in air 30°C: 28 A

 

1x1.5mm²

Nexans ref.

  • Conductor cross-section: 1.5 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 23 A
  • Permissible current rating buried/duct 20°C: 19 A
  • Perm current rating in duct 30°C: 18 A
  • Perm current rating in air 30°C: - A

 

1x2.5mm²

Nexans ref.

  • Conductor cross-section: 2.5 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 38 A
  • Permissible current rating buried/duct 20°C: 33 A
  • Perm current rating in duct 30°C: 24 A
  • Perm current rating in air 30°C: - A

 

1x4mm²

Nexans ref.

  • Conductor cross-section: 4 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 59 A
  • Permissible current rating buried/duct 20°C: 42 A
  • Perm current rating in duct 30°C: 37 A
  • Perm current rating in air 30°C: 42 A

 

1x6mm²

Nexans ref.

  • Conductor cross-section: 6 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 74 A
  • Permissible current rating buried/duct 20°C: 52 A
  • Perm current rating in duct 30°C: 48 A
  • Perm current rating in air 30°C: 55 A

 

1x10mm²

Nexans ref.

  • Conductor cross-section: 10 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 98 A
  • Permissible current rating buried/duct 20°C: 68 A
  • Perm current rating in duct 30°C: 66 A
  • Perm current rating in air 30°C: 77 A

 

1x50mm²

Nexans ref.

  • Conductor cross-section: 50 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 230 A
  • Permissible current rating buried/duct 20°C: 159 A
  • Perm current rating in duct 30°C: 175 A
  • Perm current rating in air 30°C: 216 A

 

1x16mm²

Nexans ref.

  • Conductor cross-section: 16 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 126 A
  • Permissible current rating buried/duct 20°C: 89 A
  • Perm current rating in duct 30°C: 88 A
  • Perm current rating in air 30°C: 105 A

 

1x25mm²

Nexans ref.

  • Conductor cross-section: 25 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 161 A
  • Permissible current rating buried/duct 20°C: 113 A
  • Perm current rating in duct 30°C: 117 A
  • Perm current rating in air 30°C: 141 A

 

1x35mm²

Nexans ref.

  • Conductor cross-section: 35 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 194 A
  • Permissible current rating buried/duct 20°C: 136 A
  • Perm current rating in duct 30°C: 144 A
  • Perm current rating in air 30°C: 176 A

 

1x70mm²

Nexans ref.

  • Conductor cross-section: 70 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 282 A
  • Permissible current rating buried/duct 20°C: 197 A
  • Perm current rating in duct 30°C: 222 A
  • Perm current rating in air 30°C: 279 A

 

1x95mm²

Nexans ref.

  • Conductor cross-section: 95 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 339 A
  • Permissible current rating buried/duct 20°C: 232 A
  • Perm current rating in duct 30°C: 269 A
  • Perm current rating in air 30°C: 342 A

 

1x120mm²

Nexans ref.

  • Conductor cross-section: 120 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 386 A
  • Permissible current rating buried/duct 20°C: 263 A
  • Perm current rating in duct 30°C: 312 A
  • Perm current rating in air 30°C: 400 A

 

1x150mm²

Nexans ref.

  • Conductor cross-section: 150 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 431 A
  • Permissible current rating buried/duct 20°C: 296 A
  • Perm current rating in duct 30°C: 342 A
  • Perm current rating in air 30°C: 464 A

 

1x185mm²

Nexans ref.

  • Conductor cross-section: 185 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 486 A
  • Permissible current rating buried/duct 20°C: 332 A
  • Perm current rating in duct 30°C: 384 A
  • Perm current rating in air 30°C: 533 A

 

3X2.5mm²

Nexans ref.

  • Conductor cross-section: 2.5 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 38 A
  • Permissible current rating buried/duct 20°C: 33 A
  • Perm current rating in duct 30°C: 24 A
  • Perm current rating in air 30°C: 32 A

 

3X4mm²

Nexans ref.

  • Conductor cross-section: 4 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 59 A
  • Permissible current rating buried/duct 20°C: 42 A
  • Perm current rating in duct 30°C: 35 A
  • Perm current rating in air 30°C: 42 A

 

3X6mm²

Nexans ref.

  • Conductor cross-section: 6 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 74 A
  • Permissible current rating buried/duct 20°C: 52 A
  • Perm current rating in duct 30°C: 44 A
  • Perm current rating in air 30°C: 54 A

 

3X10mm²

Nexans ref.

  • Conductor cross-section: 10 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 98 A
  • Permissible current rating buried/duct 20°C: 68 A
  • Perm current rating in duct 30°C: 60 A
  • Perm current rating in air 30°C: 75 A

 

3X25mm²

Nexans ref.

  • Conductor cross-section: 25 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 161 A
  • Permissible current rating buried/duct 20°C: 113 A
  • Perm current rating in duct 30°C: 105 A
  • Perm current rating in air 30°C: 127 A

 

3X35mm²

Nexans ref.

  • Conductor cross-section: 35 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 194 A
  • Permissible current rating buried/duct 20°C: 136 A
  • Perm current rating in duct 30°C: 128 A
  • Perm current rating in air 30°C: 158 A

 

3X50mm²

Nexans ref.

  • Conductor cross-section: 50 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 230 A
  • Permissible current rating buried/duct 20°C: 159 A
  • Perm current rating in duct 30°C: 154 A
  • Perm current rating in air 30°C: 192 A

 

3X70mm²

Nexans ref.

  • Conductor cross-section: 70 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 282 A
  • Permissible current rating buried/duct 20°C: 197 A
  • Perm current rating in duct 30°C: 194 A
  • Perm current rating in air 30°C: 246 A

 

3X95mm²

Nexans ref.

  • Conductor cross-section: 95 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 339 A
  • Permissible current rating buried/duct 20°C: 232 A
  • Perm current rating in duct 30°C: 233 A
  • Perm current rating in air 30°C: 298 A

 

3X120mm²

Nexans ref.

  • Conductor cross-section: 120 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 386 A
  • Permissible current rating buried/duct 20°C: 263 A
  • Perm current rating in duct 30°C: 268 A
  • Perm current rating in air 30°C: 346 A

 

3X150mm²

Nexans ref.

  • Conductor cross-section: 150 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 431 A
  • Permissible current rating buried/duct 20°C: 296 A
  • Perm current rating in duct 30°C: 300 A
  • Perm current rating in air 30°C: 399 A

 

3X185mm²

Nexans ref.

  • Conductor cross-section: 185 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 486 A
  • Permissible current rating buried/duct 20°C: 332 A
  • Perm current rating in duct 30°C: 340 A
  • Perm current rating in air 30°C: 456 A

 

4X6mm²

Nexans ref.

  • Conductor cross-section: 6 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 74 A
  • Permissible current rating buried/duct 20°C: 52 A
  • Perm current rating in duct 30°C: 44 A
  • Perm current rating in air 30°C: 54 A

 

1x240mm²

Nexans ref.

  • Conductor cross-section: 240 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 563 A
  • Permissible current rating buried/duct 20°C: 382 A
  • Perm current rating in duct 30°C: 450 A
  • Perm current rating in air 30°C: 634 A

 

3X1.5mm²

Nexans ref.

  • Conductor cross-section: 1.5 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 23 A
  • Permissible current rating buried/duct 20°C: 19 A
  • Perm current rating in duct 30°C: 19 A
  • Perm current rating in air 30°C: 19 A

 

3X16mm²

Nexans ref.

  • Conductor cross-section: 16 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 126 A
  • Permissible current rating buried/duct 20°C: 89 A
  • Perm current rating in duct 30°C: 80 A
  • Perm current rating in air 30°C: 100 A

 

3X240mm²

Nexans ref.

  • Conductor cross-section: 240 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 563 A
  • Permissible current rating buried/duct 20°C: 382 A
  • Perm current rating in duct 30°C: 398 A
  • Perm current rating in air 30°C: 538 A

 

4X1.5mm²

Nexans ref.

  • Conductor cross-section: 1.5 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 23 A
  • Permissible current rating buried/duct 20°C: 19 A
  • Perm current rating in duct 30°C: 19 A
  • Perm current rating in air 30°C: 19 A

 

4X2.5mm²

Nexans ref.

  • Conductor cross-section: 2.5 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 38 A
  • Permissible current rating buried/duct 20°C: 33 A
  • Perm current rating in duct 30°C: 24 A
  • Perm current rating in air 30°C: 32 A

 

4X4mm²

Nexans ref.

  • Conductor cross-section: 4 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 59 A
  • Permissible current rating buried/duct 20°C: 42 A
  • Perm current rating in duct 30°C: 35 A
  • Perm current rating in air 30°C: 42 A

 

4X10mm²

Nexans ref.

  • Conductor cross-section: 10 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 98 A
  • Permissible current rating buried/duct 20°C: 68 A
  • Perm current rating in duct 30°C: 60 A
  • Perm current rating in air 30°C: 75 A

 

4X16mm²

Nexans ref.

  • Conductor cross-section: 16 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 126 A
  • Permissible current rating buried/duct 20°C: 89 A
  • Perm current rating in duct 30°C: 80 A
  • Perm current rating in air 30°C: 100 A

 

4X25mm²

Nexans ref.

  • Conductor cross-section: 25 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 161 A
  • Permissible current rating buried/duct 20°C: 113 A
  • Perm current rating in duct 30°C: 105 A
  • Perm current rating in air 30°C: 127 A

 

4X35mm²

Nexans ref.

  • Conductor cross-section: 35 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 194 A
  • Permissible current rating buried/duct 20°C: 136 A
  • Perm current rating in duct 30°C: 128 A
  • Perm current rating in air 30°C: 158 A

 

4X50mm²

Nexans ref.

  • Conductor cross-section: 50 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 230 A
  • Permissible current rating buried/duct 20°C: 159 A
  • Perm current rating in duct 30°C: 154 A
  • Perm current rating in air 30°C: 192 A

 

4X70mm²

Nexans ref.

  • Conductor cross-section: 70 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 282 A
  • Permissible current rating buried/duct 20°C: 197 A
  • Perm current rating in duct 30°C: 194 A
  • Perm current rating in air 30°C: 246 A

 

4X95mm²

Nexans ref.

  • Conductor cross-section: 95 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 339 A
  • Permissible current rating buried/duct 20°C: 232 A
  • Perm current rating in duct 30°C: 233 A
  • Perm current rating in air 30°C: 298 A

 

4X120mm²

Nexans ref.

  • Conductor cross-section: 120 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 386 A
  • Permissible current rating buried/duct 20°C: 263 A
  • Perm current rating in duct 30°C: 268 A
  • Perm current rating in air 30°C: 346 A

 

5X1.5mm²

Nexans ref.

  • Conductor cross-section: 1.5 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 23 A
  • Permissible current rating buried/duct 20°C: 19 A
  • Perm current rating in duct 30°C: 19 A
  • Perm current rating in air 30°C: 19 A

 

5X2.5mm²

Nexans ref.

  • Conductor cross-section: 2.5 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 38 A
  • Permissible current rating buried/duct 20°C: 33 A
  • Perm current rating in duct 30°C: 24 A
  • Perm current rating in air 30°C: 32 A

 

5x2/0AWG

Nexans ref.

  • Packaging: Cut to length (m)
  • Conductor cross-section: 67.4 mm²
  • Conductor cross-section (AWG/KCMIL): 2/0
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 278 A
  • Permissible current rating buried/duct 20°C: 192 A
  • Perm current rating in duct 30°C: 190 A
  • Perm current rating in air 30°C: 240 A

 

5x1AWG

Nexans ref.

  • Packaging: Cut to length (m)
  • Conductor cross-section: 42.4 mm²
  • Conductor cross-section (AWG/KCMIL): 1
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 216 A
  • Permissible current rating buried/duct 20°C: 150 A
  • Perm current rating in duct 30°C: 144 A
  • Perm current rating in air 30°C: 178 A

 

5X4AWG

Nexans ref. 10003150

  • Packaging: Cut to length (m)
  • Conductor cross-section: 21.2 mm²
  • Conductor cross-section (AWG/KCMIL): 4
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 147 A
  • Permissible current rating buried/duct 20°C: 103 A
  • Perm current rating in duct 30°C: 95 A
  • Perm current rating in air 30°C: 114 A

 

4x150mm²

Nexans ref.

  • Packaging: Cut to length (m)
  • Conductor cross-section: 150 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 431 A
  • Permissible current rating buried/duct 20°C: 296 A
  • Perm current rating in duct 30°C: 300 A
  • Perm current rating in air 30°C: 399 A

 

1x300mm²

Nexans ref.

  • Packaging: Cut to length (m)
  • Conductor cross-section: 300 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 629 A
  • Permissible current rating buried/duct 20°C: 431 A
  • Perm current rating in duct 30°C: 514 A
  • Perm current rating in air 30°C: 736 A

 

4X185mm²

Nexans ref.

  • Packaging: Cut to length (m)
  • Conductor cross-section: 185 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 486 A
  • Permissible current rating buried/duct 20°C: 332 A
  • Perm current rating in duct 30°C: 340 A
  • Perm current rating in air 30°C: 456 A

 

5X6mm²

Nexans ref.

  • Packaging: Cut to length (m)
  • Conductor cross-section: 6 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 74 A
  • Permissible current rating buried/duct 20°C: 52 A
  • Perm current rating in duct 30°C: 44 A
  • Perm current rating in air 30°C: 54 A

 

5X10mm²

Nexans ref.

  • Packaging: Cut to length (m)
  • Conductor cross-section: 10 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 98 A
  • Permissible current rating buried/duct 20°C: 68 A
  • Perm current rating in duct 30°C: 60 A
  • Perm current rating in air 30°C: 75 A

 

5X16mm²

Nexans ref.

  • Packaging: Cut to length (m)
  • Conductor cross-section: 16 mm²
  • Conductor cross-section (AWG/KCMIL): -
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 126 A
  • Permissible current rating buried/duct 20°C: 89 A
  • Perm current rating in duct 30°C: 80 A
  • Perm current rating in air 30°C: 100 A

 

5X6AWG

Nexans ref. 10003145

  • Packaging: Cut to length (m)
  • Conductor cross-section: 13.3 mm²
  • Conductor cross-section (AWG/KCMIL): 6
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 114 A
  • Permissible current rating buried/duct 20°C: 80 A
  • Perm current rating in duct 30°C: 72 A
  • Perm current rating in air 30°C: 89 A

 

5X8AWG

Nexans ref. 10018209

  • Conductor cross-section: 8.37 mm²
  • Conductor cross-section (AWG/KCMIL): 8
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 89 A
  • Permissible current rating buried/duct 20°C: 63 A
  • Perm current rating in duct 30°C: 54 A
  • Perm current rating in air 30°C: 67 A

 

5X10AWG

Nexans ref. 10022090

  • Conductor cross-section: 5.26 mm²
  • Conductor cross-section (AWG/KCMIL): 10
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 69 A
  • Permissible current rating buried/duct 20°C: 48 A
  • Perm current rating in duct 30°C: 38 A
  • Perm current rating in air 30°C: 50 A

 

5X2AWG

Nexans ref. 10048296

  • Conductor cross-section: 33.6 mm²
  • Conductor cross-section (AWG/KCMIL): 2
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 189 A
  • Permissible current rating buried/duct 20°C: 132 A
  • Perm current rating in duct 30°C: 125 A
  • Perm current rating in air 30°C: 154 A

 

5X12AWG

Nexans ref. 10022091

  • Conductor cross-section: 3.31 mm²
  • Conductor cross-section (AWG/KCMIL): 12
  • Conductor cross-section: - kcmil
  • Permissible current rating buried 20°C: 39 A
  • Permissible current rating buried/duct 20°C: 38 A
  • Perm current rating in duct 30°C: 31 A
  • Perm current rating in air 30°C: 38 A

 

1x250kcmil

Nexans ref. 10003172

  • Packaging: Cut to length (300m)
  • Conductor cross-section: 127 mm²
  • Conductor cross-section (AWG/KCMIL): 250
  • Conductor cross-section: 250 kcmil
  • Permissible current rating buried 20°C: 396 A
  • Permissible current rating buried/duct 20°C: 270 A
  • Perm current rating in duct 30°C: 322 A
  • Perm current rating in air 30°C: 415 A

 

3X250kcmil

Nexans ref.

  • Packaging: Cut to length (300m)
  • Conductor cross-section: 127 mm²
  • Conductor cross-section (AWG/KCMIL): 250
  • Conductor cross-section: 250 kcmil
  • Permissible current rating buried 20°C: 396 A
  • Permissible current rating buried/duct 20°C: 270 A
  • Perm current rating in duct 30°C: 277 A
  • Perm current rating in air 30°C: 358 A

 

4X250kcmil

Nexans ref. 10049189

  • Conductor cross-section: 127 mm²
  • Conductor cross-section (AWG/KCMIL): 250
  • Conductor cross-section: 250 kcmil
  • Permissible current rating buried 20°C: 396 A
  • Permissible current rating buried/duct 20°C: 270 A
  • Perm current rating in duct 30°C: 277 A
  • Perm current rating in air 30°C: 358 A

 

1x350kcmil

Nexans ref. 10003175

  • Packaging: Cut to length (300m)
  • Conductor cross-section: 177 mm²
  • Conductor cross-section (AWG/KCMIL): 350
  • Conductor cross-section: 350 kcmil
  • Permissible current rating buried 20°C: 474 A
  • Permissible current rating buried/duct 20°C: 325 A
  • Perm current rating in duct 30°C: 374 A
  • Perm current rating in air 30°C: 518 A

 

3X350kcmil

Nexans ref.

  • Packaging: Cut to length (300m)
  • Conductor cross-section: 177 mm²
  • Conductor cross-section (AWG/KCMIL): 350
  • Conductor cross-section: 350 kcmil
  • Permissible current rating buried 20°C: 474 A
  • Permissible current rating buried/duct 20°C: 325 A
  • Perm current rating in duct 30°C: 331 A
  • Perm current rating in air 30°C: 444 A

 

4X350kcmil

Nexans ref. 10048003

  • Conductor cross-section: 177.3 mm²
  • Conductor cross-section (AWG/KCMIL): 350
  • Conductor cross-section: 350 kcmil
  • Permissible current rating buried 20°C: 474 A
  • Permissible current rating buried/duct 20°C: 325 A
  • Perm current rating in duct 30°C: 331 A
  • Perm current rating in air 30°C: 444 A

 

1x500kcmil

Nexans ref. 10003176

  • Packaging: Cut to length (300m)
  • Conductor cross-section: 253 mm²
  • Conductor cross-section (AWG/KCMIL): 500
  • Conductor cross-section: 500 kcmil
  • Permissible current rating buried 20°C: 576 A
  • Permissible current rating buried/duct 20°C: 393 A
  • Perm current rating in duct 30°C: 464 A
  • Perm current rating in air 30°C: 657 A

 

3X500kcmil

Nexans ref.

  • Packaging: Cut to length (300m)
  • Conductor cross-section: 253 mm²
  • Conductor cross-section (AWG/KCMIL): 500
  • Conductor cross-section: 500 kcmil
  • Permissible current rating buried 20°C: 576 A
  • Permissible current rating buried/duct 20°C: 393 A
  • Perm current rating in duct 30°C: 410 A
  • Perm current rating in air 30°C: 557 A

 

Description

Description

Standards

  • Product
    IEC 60228; IEC 60502-1
  • Test
    IEC 60332-1-2

Applications

Flexible power and control cable for fixed installations. Recommended in loops demanding extra-flexible cables. To be used especially in industrial buildings and substations. It can be installed in free air, in ducts or directly buried. It can be installed submerged in water.
In small sizes, it is used as control cable for the inner part in cabinets.

Construction: Singlecore or multicore copper conductor from 3 to 5 cores.

Conductor: Class 5 flexible copper conductor according to IEC 60228.

Insulation: Crosslinked Polyethylene (XLPE) with excellent electrical properties, good resistance to ozone and chemical agents. Cores identification by colors.

Oversheath: Black color Polyvinyl Chloride (PVC), flame retardant, resistant to weather and UV radiation. available in other colors upon request.

Marking:

Nexans MULTI-FLEX SERIE 2 RV-K "size" 0.6/1 kV (Um=1,2kV) 90°C INGCER  E-021-14-4022 "Manuf. order" "Date" CHILE "sequential footage"

Design Alternatives

MULTIFLEX-RAT: Resistant to rodent attack.

MULTIFLEX-BLIND: Shielded with copper tape.

MULTIFLEX-BLIND-TZ: Shielded with a tinned copper braid.

Other rated voltages upon request: 1,8/3 kV.

Fire Safety alternative:

FREETOX-FLEX SERIE 3  RZ1-K 

 

INSTALATION CONDITIONS FOR CURRENT CARRYING CAPACITIES

Current carrying capacities based on table N°4.4 according to RIC N°4, They are applied for installations where ducts and cables are not directly exposed to solar radiation.

(3) direct current buried at 20°C: Sheathed, single conductor or multi conductor cables (Three conductors with load) installed directly buried. Installation Method D2 according to RIC N°4.

(4) current in buried duct at 20°CSingle conductor or multi conductor cables (three conductors with load) installed in buried ducts. Installation Method D1 according to RIC N°4.

(5) duct current at 30°CUp to three single conductors or multi conductor cables (three conductors with load) installed in ducts or trays attached to walls. Installation Method B1 and B2 according to RIC N°4.

(6) air current at 30°C: Multiconductor cables (Three conductors with load) installed freely in the air, in conductor ladders or in conductor baskets or in perforated trays. Installation Method E according to RIC N°4. Single conductor cables: Three conductors with load, in contact and in a flat arrangement, installed freely in the air, on conductor ladders or in conductor baskets or in perforated trays. Installation Method  F according to RIC N°4.

For buried installations, a depth of 0,7 meters and a thermal resistivity of the soil of 1 K*m/W.

Current capacity correction factors must be considered according to the specific installation conditions.

INSTALATION CONDITIONS FOR CURRENT CARRYING CAPACITIES

NOTES

Values not defined as "maximum", "max.", "minimum" or "min." are not normative requirements in the standard and they are indicative only.

CERTIFICATE SEC RV-K

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Insulation
XLPE
Outer sheath
PVC

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Class 5 IEC 60228
Mechanical resistance to impacts
UL 2556

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-15 °C
Flame retardant
IEC 60332-1-2
U.V resistance
UL 1581
Oil resistance
ICEA S-93-639 (70°C/4h)

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close