PREMIUM SUPERNYA H07V-U 1,5mm2 RJ R50M

Description

Description

Standards

  • Product
    IEC 60227-3; IEC 60228
  • Test
    IEC 60332-1-2; IEC 60332-3-24 Cat.C

Use / Applications
Indoor installations in a dry environment, placed inside pipes. For indoor use. 

 

Construction
Formation: Single-core copper.
Conductor: Soft copper wire, class 1 according to IEC 60228.
Insulation: Thermoplastic compound of polyvinyl chloride (PVC), highly flame retardant and non-fire spread. Available in blue, black, red, white, or green colors.

 

Marking: Nexans PREMIUM SUPER NYA H07V-U "section" 450/750 V INGCER E-021-14-3149 "date" CHILE "Sequential Length"

 

Flexible Fire Safety cables alternative:
FREETOX-FLEX® H07Z1 - K.

INSTALATION CONDITIONS FOR CURRENT CARRYING CAPACITY (70°C SINGLE CORE)

Current carrying capacities based on table N°4.4 of RIC N°4, for installation and cables not directly exposed to solar radiation.

Perm rating in duct 30°C (Current in duct at 30°C): Up to three single conductors with load installed in ducts or channels attached to walls, ambient temperature 30°C.. Installation Method B1 according to RIC N°4

Permissible current rating in duct (Current in embedded duct at 30°C): Up to three single conductors with load installed in ducts embedded in walls, ambient temperature 30°C. Method A1 according to RIC N°4

Current capacity correction factors must be considered according to the specific installation conditions.

INSTALLATION CONDITIONS 70°C SINGLE CORE

NOTES / VOLTAGE DROP

The indicated values ​​consider single-phase circuits in alternating current at 50Hz. To calculate the voltage drop in Volts, you must multiply the value indicated in the table [V/A.km] by the current to be transported in [A] by the length of the circuit in [km]

PACKAGING - PREMIUM SUPERNYA

Certificate SEC H07V-U

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Conductor flexibility
Solid class 1
Number of conductors
1
Insulation
PVC

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
1.5 mm²
Phase Conductor Cross Section
1.5 mm²
Nominal diameter of wires
1.4 mm
Average insulation thickness
0.7 mm
Outer Diameter
3 mm
Approximate weight
20 kg/km
Nominal outer diameter
3.0 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
450/750 V
Max. DC resistance of the conductor at 20°C
12.1 Ohm/km
Conductor AC resistance at 50 Hz
14.6 Ohm/km
Perm current rating in duct 30°C
16 A
Permissible current rating in duct 
14 A
Voltage Drop
29.2 V/A.km

Usage characteristics

Usage characteristics

Max. conductor temperature in service
70 °C
Short-circuit max. conductor temperature
160 °C
Laying operation bending radius
12 mm
Fire retardant
IEC 60332-3-24 (cat C)
Flame retardant
EN 60332-1-2

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close